REV P1 — DRAFT

5MW Diesel Power Station — General Arrangement

Project
5MW Power Station
Drawing No.
PUP-PS-GA-001
Scale
~22px / metre
Status: Draft — For Technical Assessment Only Site: 30m × 40m (1,200 m²) Capacity: 4 × 1,250 kW = 5,000 kW
N SITE BOUNDARY — 30m SITE BOUNDARY — 30m SITE BOUNDARY — 40m 30,000 40,000 ACCESS ROAD — 3.5m WIDE VEHICLE ACCESS GATE PERS. GATE CAT 3512B 1,250 kW PACKAGE incl. radiator G1 CAT 3512B 1,250 kW PACKAGE incl. radiator G2 CAT 3512B 1,250 kW PACKAGE incl. radiator G3 CAT 3512B 1,250 kW PACKAGE incl. radiator G4 4m 4m 4m 415V LV CABLE TRUNK 4m ACCESS 4m ACCESS 415V COMBINER SWITCHBOARD 20ft Container MSB LV OIL CONTAINMENT BUND HV 24kV 415V LV STEP-UP Tx 5 MVA ONAN Oil-Immersed 415V / 24kV (Dyn11) Wilson TX Co. ~10,500kg incl. oil TX1 3×1/C 95mm² Cu/XLPE 24kV EzyStrut N3 Cable Ladder 300mm HDG R_bend = 750mm A/C CONTROL ROOM SCADA/PLC Atom Modular 6×3m 18m² Office LBS CB LBS CB LBS AEGIS RMU 24kV IBB Lucy Electric ⚠ DANGER 24kV LBS CB LBS CB LBS AEGIS 24kV RMU-1 HV FEEDER TO NETWORK FUEL TANK 22kL SELF-BUNDED 20kL Safe Fill FT-1 LUBE OIL / COOLANT STORE FUEL SUPPLY TRUNK LUBE OIL / COOLANT TRUNK CONTROL / INSTRUMENTATION TRUNK E1 E2 E3 E4 EARTH RING CONDUCTOR — 70mm² BARE COPPER (BURIED) SIMPLIFIED SINGLE LINE DIAGRAM G1 1250kW G2 1250kW G3 1250kW G4 1250kW 415V BUS B/S 5 MVA 415V 24kV AEGIS 24kV IBB RMU Lucy Electric | 630A | SF6 LBS CB LBS CB LBS LINE IN Tx1 LINE Tx2 LINE OUT TO NETWORK AUX SUPPLY

Equipment Schedule

Tag Description Rating / Size
G1–G4 CAT 3512B Diesel Generator Set 1,250 kW each @ 415V, 50Hz, 0.8pf
MSB 415V Main Switchboard 4 × ACB incomers + bus section + Tx feeder
TX1 Wilson 5MVA Oil-Immersed Transformer (ONAN) 5 MVA, 415V / 24kV, Dyn11, ~10,500kg, oil bath
RMU-1 Lucy Electric Aegis 24kV IBB RMU 24kV, 630A, 21kA/3s, SF6, 5-way (3×LBS + 2×CB)
FT-1 Self-Bunded Fuel Tank 22kL (20kL safe fill), integrated 110% containment
CR Atom Modular 6×3m Portable Office 18m², SCADA/PLC, 50mm EPS panels, Teco A/C, LED lighting
LS-1 Lube Oil / Coolant Store Bunded storage room, south-side service access
E1–E4 Earth Rods 3m copper-bonded, 16mm dia
HV-C1 HV Cable (TX1 to RMU-1) 3×1/C 95mm² Cu/XLPE/CWS/PVC 12.7/22kV, ~7m per core
CL-1 EzyStrut NEMA 3 Cable Ladder 300mm W × 130mm H, HDG steel (N3L3003H), 6m run

Legend

Symbol Description
Generator Set (CAT 3512B + Alternator)
415V Switchboard / LV Equipment
Step-Up Transformer (Wilson 5MVA ONAN Oil-Immersed)
RMU — Lucy Electric Aegis 24kV IBB
Fuel Storage (Bulk / Day Tank)
HV Cable Route (24kV)
EzyStrut NEMA 3 Cable Ladder (300mm HDG)
LV Cable Route (415V)
Control / Instrumentation Trunk (SCADA)
Access Road
Site Boundary (30m × 40m)
Oil Containment Bund
Earth Ring Conductor (buried)

General Notes

  1. This drawing is a draft general arrangement for technical assessment only. Not for construction.
  2. Genset rating: 4 × CAT 3512B rated at 1,250 kW (prime) each, total installed capacity 5,000 kW at 415V, 50Hz, 3-phase.
  3. Step-up transformer: 5 MVA, ONAN, 415V Δ / 24kV Y (Dyn11 vector group). Oil-filled with containment bund sized to 110% of oil volume per AS 1940.
  4. RMU: Lucy Electric Aegis 24kV IBB standalone kiosk. SF6 gas-insulated, 630A, 21kA/3s fault rated. 5-way configuration: 3× Load Break Switch (LBS) + 2× Circuit Breaker (CB). Remote switching on all CBs and isolators. 24kV/240V auxiliary transformer for protection relays. IP54 kiosk with double front doors, side ventilation, galvanised steel grating floor, concrete plinth. Compliant with AS 62271.200, IEC 62271-200.
  5. HV cable from transformer to RMU and from RMU to site boundary: single-core XLPE, sized per AS/NZS 3008 for full plant output.
  6. Fuel storage: 22kL self-bunded fuel tank (20kL safe fill) per AS 1940 with integrated 110% containment. Lube oil and coolant stored in dedicated bunded store with south-side service access.
  7. Earthing system: Buried earth ring conductor around site perimeter — 70mm² bare copper. Earth rods at corners — 3m copper-bonded. Target earth resistance ≤1Ω. Designed per AS/NZS 3000 and ENA NENS 09.
  8. Minimum clearances: 3m around transformer (fire separation), 1.5m service clearance around gensets, 2m clearance around switchboard (rear access).
  9. All electrical installations to comply with AS/NZS 3000, AS/NZS 3008, AS 2067, and relevant state electrical safety regulations.
  10. Acoustic enclosures on all gensets to achieve ≤85 dB(A) at 1m. Site boundary noise to be assessed per local council requirements.
  11. Ventilation: Powerhouse ventilation to maintain ambient temperature below 40°C. Louvres and exhaust fans as required per CAT installation guide.
  12. Fire protection: Detection and suppression system per AS 1670 and BCA requirements. Fire water tank with pump set and ring main.